With the 3I0 harm. dropout ratio parameter, you define the dropout threshold for the Min. 3I0>
harmonic parameter.
Lowering this dropout threshold enlarges the range and the period of direction determination under fluctu-
ating zero-sequence harmonics. Siemens recommends using the default setting.
Parameter: Directional mode
Default setting (_:106) Directional mode = forward
With the Directional mode parameter, you define for which direction result the function generates the
pickup state:
If the Directional mode parameter is set as forward or reverse, the stage picks up when the direc-
tion result equals the parameterized direction, and the
Pickup
is signaled with the determined direction.
If the Directional mode parameter is set as non-directional, the stage picks up regardless of the
direction result, and the
Pickup
is signaled with the unknown information.
Parameter: Operate delay
Default setting (_:6) Operate delay = 1.00 s
The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.
i
i
NOTE
When both the Operate delay and the Dir.-result extension are applied, the Operate delay
should usually be set to a considerably greater value than the Dir.-result extension. If the Operate
delay is less than the Dir.-result extension, the function will operate for each fault regardless of
the fault duration, as long as the fault direction equals the set direction.
Parameter: Operate & flt.rec. blocked
Default setting (_:2) Operate & flt.rec. blocked = no
With the Operate & flt.rec. blocked parameter, you block the operate indication, the fault recording,
and the fault log. In this case, a ground-fault log is created instead of the fault log.
Parameter: Blk. by meas.-volt. failure
Default setting (_:10) Blk. by meas.-volt. failure = yes
You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:
The device-internal supervision function Measuring-voltage failure detection is configured and
enabled.
The binary input signal
>Open
of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.
Parameter Value
Description
yes
The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no
The protection stage is not blocked.
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
606 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017