NOTE
Not all logs of your SIPROTEC 5 device can be deleted. These limitations apply especially to logs with rele-
vance for security and after-sales (security log, device-diagnosis log, setting-history log).
i
i
NOTE
Upon deletion of the fault log, the associated fault records are also deleted. In addition, the meters for fault
number and fault-record number are reset to 0. In contrast, if you delete fault records, the content of the
fault log, including the allocated fault numbers, remains.
i
i
NOTE
If the device executes an initial start, for example, after an update of the device software, the following
logs are automatically deleted:
Operational log
Fault log
Ground-fault log
Setting-history log
User log
Motor-startup log
Back up the deletable logs using DIGSI 5.
i
i
NOTE
If a ground fault is currently active, the ground-fault log cannot be deleted.
Deleting Logs on the On-Site Operation Panel
To reach the selected log from the main menu, use the navigation keys of the on-site operation panel
(example operational log):
Main Menu → Indications → Operational log
Figure 3-20
Deleting the Operational Log on the On-Site Operation Panel
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
The option to delete the entire log is offered to you in the footer of the display at the bottom left. Use the
softkeys below under the display to activate the command prompts. Confirm the request to Delete.
System Functions
3.1 Indications
SIPROTEC 5, Overcurrent Protection, Manual 81
C53000-G5040-C017-8, Edition 07.2017