Figure 6-311
Cyclic Reclosing Function: Logic for the Closing Indication
Testing the Circuit-Breaker Readiness Directly before Closing
For each of the automatic reclosing cycles, you can set if a test of the circuit-breaker readiness should occur
directly before closing (parameters CB ready check bef.close, Figure 6-312). Independent of this, a
test of the circuit-breaker readiness before the start of the 1st automatic reclosing cycle can be set, see
Chapter 6.45.4.5 Start and chapter 6.45.4.16 Circuit-Breaker Readiness .
Protection and Automation Functions
6.45 Automatic Reclosing Function
906 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017