Resetting/Setting the Counters
You can reset or set the counters of group 1 and group 2 via:
On-site operation panel directly on the device
Online DIGSI connection to the device
Binary input
>Reset all counters
(only reset of all counters)
Communication connection with the control center
You can directly set or reset the counters via IEC 61850 by setting the counter values to the desired value. If
you want to reset the counters via DNP3, IEC 60870-5-103, Modbus, or IEC 60870-5-104, an additional config-
uration with CFC is necessary. For more information, refer to chapter 7.4.3.2 Application and Setting Notes.
Functional Measured Values
Values Description Primary Secondary % Referenced to
(_:2311:300) Iunbl.cp Compensated unbalanced
current I
unbal.,comp.
kA A Parameter Rated primary
current
(_:2311:301) Iunbl. Non-compensated unbal-
anced current I
unbal.
kA A Parameter Rated primary
current
(_:2311:323) Cp.vect. Compensation vector
I
comp.,vect.
kA A Parameter Rated primary
current
You can find the value of the parameter Rated primary current of the preceding table in the chapter
6.1.8 Settings according to the specified parameter MP selection.
I
comp.,vect.
is normalized with I
c
. The normalization is carried out no matter if the parameter Normalization
with Ic is set to yes or no. I
comp.,vect.
keeps its value unchanged until the next compensation occurs.
[fo_compensation vector, 1, en_US]
Where:
I
unbal.op.
Operational unbalanced current at the moment the compensation is carried
out
I
c,rated
Rated current of the capacitor bank
I
c
Current of the capacitor bank at the moment the compensation is carried
out
Definition of the Group and Fault Location with the Capacitor in H Connection
If the capacitor is designed in an H connection, the following definition is assumed:
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase
SIPROTEC 5, Overcurrent Protection, Manual 983
C53000-G5040-C017-8, Edition 07.2017