Logging 9410 series
Data recorder
number
Log name Depth Interval
10 Energy/Demand (EgyDmd
Log)
3360 (35 days) 900 seconds (15 minutes)
5
Sag/Swell Log 100 Triggered on demand
N/A Event Log 500 Triggered on demand
11, 12, 17, 19 - 26,
28, 29, 32, 35
EN50160 Logs varies EN50160 intervals
6, 16, 37, 38, 40 4-30 Logs varies IEC61000-4-30 intervals
Your meter can support up to 50 data logs (data recorders) which can each record up
to 16 different parameters.
Default data logging configuration
Your meter is equipped with preconfigured data logs which you can modify.
The default data logging configuration might be used by other components of your
power monitoring system. Do not change the default configuration of any of the logs,
unless you understand the impact of the change on these power monitoring system
components and the data they use and on your meter’s memory.
Revenue log
The Revenue Log is configured for use with UTS MV-90 billing software. The default
values logged by the Revenue Log are as follows:
Parameter Description
kWh del int Interval kWh delivered
kWh rec int Interval kWh received
kVARh del int Interval kVARh delivered
kVARh rec int Interval kVARh received
Historic data logs
Three historic data logs are used to record standard power system quantities, such as
phase current, phase voltage and power factor. These logs are labeled Hist Mean Log,
Hist High Log, and Hist Low Log. By default, they log the following values:
Hist Mean Log
Vll ab mean I avg mean
Vll bc mean I 4 mean
Vll ca mean kW tot mean
Vll avg mean kVAR tot mean
V unbal mean kVA tot mean
Ia mean PF lag mean
Ib mean PF lead mean
Ic mean Freq mean
Hist High Log
Vll ab high I avg high
Vll bc high I 4 high
7EN05-0336-03 125