Meter overview 9410 series
COMTRADE: this allows the meter to save waveform data in COMmon format for
TRAnsient Data Exchange (COMTRADE) on its internal FTP server.
Your meter includes the following power quality compliance:
EN50160: Your meter measures and presents statistics for determining EN50160
compliance.
IEC 61000-4-30: Your meter complies with the IEC 61000-4-30 power quality
standard.
IEC 62586: Your meter complies with the IEC 62586 power quality standard.
Localization
The meter can be customized to use different regional settings.
Localization settings determine:
The language used for the display and webpages
Time, date and digit formats
Displayed phase labels (123/ABC)
IEEE (Institute of Electrical and Electronics Engineers) or IEC (International
Electrotechnical Commission) conventions for power, power factor and energy
You can configure your meter’s localization settings through the display or using ION
Setup.
Data display and analysis tools
Display
Use the meter’s display for local monitoring and standalone applications.
The color LCD display lets you view real-time values, events and alarms, and perform
basic device configuration. Connect a remote display to a meter without an integrated
display to view meter data and perform basic meter configuration.
Active and historical alarms
The meter’s display shows an alarm icon and the alarm LED flashes if your meter
detects an active alarm condition.
Depending on the priority of the alarm, your meter’s display also flashes. You can view
and acknowledge active alarms and historic alarms and events through the display
and software webpages. An active alarm becomes a historic alarm when the alarm
condition no longer exists.
Meter internal web server feature
Your meter’s internal web server provides quick and easy access to real-time energy
and basic power quality information without special software using an on-board web
server combined with an Ethernet port.
The built-in web pages display selected energy and power quality information through
the web-enabled device; these pages also support basic meter configuration.
7EN05-0336-03 15

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 9410 Series and is the answer not in the manual?

Siemens 9410 Series Specifications

General IconGeneral
BrandSiemens
Model9410 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals