9410 series Basic setup
Basic setup
Default values for commissioning
Use these default settings for the first time you connect to and configure your meter.
Parameter Default value
Display password (also for logging onto meter webpages) 0
Username (for logging onto meter webpages) 9410
IP address 169.254.0.10
Subnet mask 255.255.0.0
Gateway 0.0.0.0
Unit ID 1
Language English
Meter setup
You can configure your meter’s basic metering parameters using the display.
Volts mode
Parameter Values Description
Volts Mode 4W-Wye, Delta, 3W-Wye,
Single, Demo
The power system’s configuration
PhaseOrder ABC, ACB The power system’s phase order
PT/CT setup
Parameter Values Description
PT Primary 1 to 999,999.99 The potential transformer’s primary winding voltage
rating
NOTE: PTs are also referred to as a VTs or
voltage transformers.
PT Secondary 1 to 999,999.99 The potential transformer’s secondary winding
voltage rating
NOTE: PTs are also referred to as a VTs or
voltage transformers.
CT Primary 1 to 999,999.99 The current transformer’s primary winding current
rating
CT Secondary 1 to 999,999.99 The current transformer’s secondary winding
current rating
I4 Primary 1 to 999,999.99 The I4 current transformer’s primary winding
current rating
I4 Secondary 1 to 999,999.99 The I4 current transformer’s secondary winding
current rating
18 7EN05-0336-03