Security 9410 series
10. If you have selected standard security, click Finish. You are prompted to save
your security configuration to a file which can be loaded onto other meters.
NOTE: If you chose to save your security file, enter a descriptive name and
click Save. It is recommended that you do not overwrite the default security
files.
If you have selected advanced security, click Next to configure user access and
passwords.
Security parameters available using ION Setup
Parameter Standard/advanced Details
Meter password Standard/advanced Default meter password is 0 (zero).
Active web server Standard/advanced This option allows you to enable or disable your meter’s webpages.
Allow web server
programming
Standard/advanced This option allows you to enable or disable the ability to configure your meter using
the meter’s webpages.
NOTE: To enable allow web server programming, you must have active web
server enabled.
Allow Modbus
programming
Advanced only This option can only be enabled in advanced security and is disabled for standard
security.
Allow front panel
programming
Standard/advanced This option allows you to enable or disable the ability to configure your device using
the display.
Allow broadcasting time
synchronization
Advanced only This option can only be disabled in advanced security and is enabled for standard
security.
Protocol-specific security parameters available using ION Setup
Parameter Values Description
Protocol lockout 0 - 255 The number of invalid login attempts before access is denied.
If protocol lockout = 0, there is no limit to the number of invalid login attempts and the
protocol will never be locked out.
Session timeout 1 - 43200 minutes (30
days)
The interval between access checks for non-session based protocols.
Related Topics
• Recommended security configuration
• Protocols, ports and connections
Configuring users and passwords using ION Setup (advanced
security only)
Use ION Setup to configure users and passwords.
In order to change security settings, you must be logged into ION Setup with an
appropriate ION Setup user level. You must also have the appropriate meter-level
security access to configure meter security.
You must have configured the standard security settings on your meter using ION
Setup.
This task assumes that you are in the user configuration screen in the security wizard
in ION Setup.
1. In the user/passwords screen, select (check) the user that you want to configure
to view the user access options.
7EN05-0336-03 49