EasyManuals Logo

Siemens 9410 Series User Manual

Siemens 9410 Series
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
9410 series Time and timekeeping
UNLOCKED if the time difference between the GPS time sync source and meter clock
is greater than ±1 ms of each other
Configuring time information using your meter’s display
Use the meter’s display to configure a variety of time parameters.
1. Go to Setup Menu > Date/Time/Clock Setup > Date & Time Setup.
2. Configure your time and date formats, time zone offset, and daylight savings time
offset. Press the down button to access the Clock Setup screen.
3. Configure the clock and time synchronization source, and the time
synchronization time format.
Date & time setup
Parameter Values Description
Time Format 12 H, 24 H Specifies how the time is displayed
Date Format
MM/DD/YYYY, DD/MM/
YYYY, YYYY/MM/DD
Specifies how the date is displayed
TZ Offset -12:00:00 to 12:00:00 Sets the time zone of the meter’s location,
relative to UTC
DST Offset -3:00:00 to 3:00:00 Sets the daylight savings time offset of the
meter’s location
Clock setup
Parameter Values Description
Clock Source Internal, Line Freq, COMM Specifies the time synchronization source
Time Sync
Source
COM1, Ethernet,
Ethernet - ION, Ethernet -
DNP, IRIG-B
Specifies the port to receive time
synchronization signals
Time Sync Type UTC, Local Specifies whether time synchronization signals
are received in local time or UTC
Date/Time/Clock setup
You can configure your meter’s date, time and clock parameters using the display.
Date & time setup
Parameter Values Description
Time Format 12 H, 24 H Specifies how the time is displayed
Date Format
MM/DD/YYYY, DD/MM/
YYYY, YYYY/MM/DD
Specifies how the date is displayed
TZ Offset -12:00:00 to 12:00:00 Sets the time zone of the meter’s location, relative
to UTC
DST Offset -3:00:00 to 3:00:00 Sets the daylight savings time offset of the meter’s
location
96 7EN05-0336-03

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 9410 Series and is the answer not in the manual?

Siemens 9410 Series Specifications

General IconGeneral
BrandSiemens
Model9410 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals