Communications 9410 series
GPS: Arbiter (this protocol setting is for connecting to a GPS receiver
communicating in serial ASCII format)
GPS: Arbiter-Vorne (this protocol setting is for connecting to a GPS receiver
communicating in serial ASCII format)
None this protocol setting stops communications using this port
Related Topics
Protocols, ports and connections
RS-485 Bias
You can use the RS-485 bias setting to fine tune communications.
Turn on the RS-485 bias when the meter is acting as a master over RS-485
communications and turn off the RS-485 bias when the meter is acting as a slave. You
can configure RS-485 biasing through the meter’s display or ION Setup.
Configuring serial communications using the display
You can configure your meter’s basic serial communications settings using the display.
Before configuring serial parameters, make sure you have a unique unit ID for your
meter and know the serial network settings (protocol, baud rate, parity and stop bits).
1. Go to Setup Menu > Communications Setup > COM1 Setup.
2. Configure your meter’s serial settings as required.
Serial communications settings
Parameter Values Description
Protocol ION, Modbus RTU, Modbus
Master, DNP v3.00,
EtherGate, GPS: Truetime/
Datum, GPS: Arbiter, GPS:
Arbiter-Vorne, Factory,
None
Sets the communications protocol for your
meter’s RS-485 port
NOTE: the NONE setting stops
communications using this port.
Baud Rate 2400, 4800, 9600, 19200,
38400, 57600, 115200
Sets the data rate, in bits per second
Rx Timeout 0 to 1 Sets the transmit delay in seconds
Unit ID 1 to 9999 Sets the meter’s unique ID on the RS-485
network
NOTE: Modbus serial device range 1 to
247
Serial Port 8N1, 8N2, 8E1, 8E2, 8O1,
8O2
Sets the parity and stop bits for the port
RS485 Bias Off, On Turns on biasing when mastering devices over
the RS-485 port
Configuring serial communications settings using ION Setup
You can use ION Setup to configure your meter’s serial communications settings.
Before configuring serial parameters, make sure you have a unique unit ID for your
meter and know the serial network settings (protocol, baud rate, parity and stop bits).
1. Start ION Setup.
2. Open the Setup Assistant for your device.
7EN05-0336-03 67