Communications 9410 series
You must have:
The IEC 68150 configuration file stored in a location accessible by ION Setup. The
configuration file is created by customizing the IEC 61850 device (ICD) file, which
can be downloaded from www.usa.siemens.com/pds.
FTP access to your meter from the computer running ION Setup.
NOTE: Your meter can have only one IEC 61850 configuration (CID) file loaded
onto its internal FTP site. If additional CID files are loaded, IEC 61850 functions
are deactivated until the additional files are removed.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Communications > 3rd Party Protocols and select the IEC 61850
tab.
4. Highlight a parameter and click Upload. Navigate to where you stored your
meter’s CID file, select the file, and click Open.
Your meter reviews the CID file to determine if it is valid. This process may take
several minutes.
The CID status indicates whether the meter has received and validated an IEC
61850 CID file and is operating as an IEC 61850 server.
Configuring additional data for IEC 61850 using ION Setup
You can map additional data to IEC 61850 using ION Setup.
You must have a valid IEC 61850 configuration file loaded onto your meter for IEC
61850 functionality, but it is not necessary for configuring additional data.
NOTE: You can configure additional data at any time, whether or not IEC 61850 is
operating on your meter.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Communications > 3rd Party Protocols and select the IEC 61850
tab.
4. Select the information type that corresponds to the type of meter information that
you want to add to your IEC 61850 data. Select analog for numeric information
and digital for boolean or binary information. Click Edit. The custom configuration
screen is displayed.
5. Select the desired meter value from those available. If the value you want is not
shown, select Show all available registers.
6. Select an IEC 61850 leaf to associate with the meter data, and click >> to map the
value. Click << to unmap values. Click OK to send and save your changes to the
meter.
Configuring digital outputs for IEC 61850 control using ION Setup
You can configure your digital outputs so that they can be used for non-critical control
via IEC 61850.
Your meter has a comprehensive default implementation of IEC 61850 which meets
the needs of most systems with only basic configuration. You can customize this
implementation so that IEC 61850 can be used to control your meter’s digital outputs;
7EN05-0336-03 91

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 9410 Series and is the answer not in the manual?

Siemens 9410 Series Specifications

General IconGeneral
BrandSiemens
Model9410 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals