3.4.10 Line module «Collective» E3M080
Pos. Component Preparation Default
1 DIL switch S3
I-Bus address
Set according to system documentation address 0
2 DIL switch S4-2
Line short-circuit evaluation
Change to ON if short circuit is to be inter-
preted as ALARM
Set to OFF
short-circuit = fault
2
1
Note:
If lines are not yet being used, termi-
nate with corresponding EOL.
3.4.11 MS5 Adapter E3M220
Pos. Component Preparation Default
1 Programming switch S1
Analysis of line 1
Set according to system documentation
See also hardware description (document
e1260)
Interpreted as fault
2 Programming switch S2
Analysis of line 2
Set according to system documentation
See also hardware description (document
e1260)
Interpreted as fault
1
2
Note:
Use 19-core connecting cable and leave
cores 12...20 unused in connector