4.4.4 Address allocation through activation
Requirements
Detector bases mounted
As a rule, the detectors have already been inserted in the bases when address al-
location by activation is started. It is, however, also possible for a detector to be in-
serted during address allocation and then activated.
Fixed devices mounted, electronics inserted
During address allocation all devices that have been inserted and installed but not yet
localized and allocated in the control unit, must be activated.
Connected fixed devices and inserted automatic detectors must be localized, other-
wise faults will arise in the localization structure.
Switch control unit to ’Address allocation through activation’ mode ( page 91)
Wait until the control unit is ready
Localize the first device
Activate detectors, manual call points or input / output module( page 101)
Wait until the response indicator flashes
Can take up to 20 seconds depending on configuration
Response indicator flashes for about 5 seconds
No other devices must be activated for at least 20 seconds
The device must not be removed again until address allocation has been completed.