Siemens Cerberus CS1140 - Emergency Operation; Emergency Operation Circuit Configurations

Siemens Cerberus CS1140
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e1249d1
16
Fire & Security Products
Siemens Building Technologies Group
01.1999
3.4.18 Control module «VdS» E3L030
Pos. Component Preparation Default
1 DIL switch S3
I-Bus address
Set according to system documentation address 0
2 Jumper X12
Configure LED4
insert if LED4 (spare / FBF) in the ’emer-
gency operating system’ must light
X12 not inserted in fac-
tory
3 Resistor R191 (3.3K) Remove (or change), if an extinguishing
system produced by another manufacturer
requiring a resistor with a different imped-
ance is connected
R191 inserted in factory
2
3
1