Fire & Security Products
Siemens Building Technologies Group
01.1999
4.3.3 Address allocation through activation
Requirements
Automatic detectors:
Detector bases installed
Detectors inserted
As a rule, detectors are already inserted in their bases when address allocation
through activation begins; but it is possible to insert a detector during address
allocation and then activate it
Fixed devices (manual fire alarms, input/output modules):
Terminal block mounted
Electronics installed
Switch control unit to ’Address allocation through activation’ mode ( page 91)
Wait until the control unit is ready
Localize the first device
Activate detectors, manual call points or input/output modules ( Page 101)
Wait until the response indicator flashes
before the response indicator flashes, no additional devices may be activated
the device must remain inserted for at least 30 seconds