7.6 Requirements for allocation
Every logical element to be localized must already be linked to a physical structure de-
vice ( page98)
The SWE11 prevents the allocation of localization data to elements which are not
linked to a physical device (trouble message: ’Nodes are not localizable check
node types’)
Measure: link logical element to a physical structure device (make sure device types
are compatible!)
The device type of the physical device linked with the element must agree with that in
the localization structure
If the device types do not match, the SWE11 prevents the allocation of the localiza-
tion data (trouble message: ’Nodes are not localizable check node types’)
Action to be taken: either alter the type of device in the physical structure or replace
the device and re-localize
The type and I-Bus address of the function units in the physical and localization struc-
tures to which the localized devices are allocated, must be identical
If the function unit types/I-Bus addresses do not match, the SWE11 prevents alloca-
tion of the localization data (trouble message: ’Nodes are not localizable check
node types’)
Action to be taken: use a physical device to which the correct functional units are allo-
cated and link it to the element to be localized
If, in the physical structure, the SWE11 does not find a function unit of the same type
and with the same I-Bus address, it is identified in the localization structure with a ’*’
Action to be taken: alter the type/I-Bus address of the relevant function unit in the
physical structure
Device types do not match
If, in the physical structure, the
SWE11 does not find a func-
tion unit of the same type and
with the same I-Bus address
as in the localization structure,
it is identified with a *
Trouble message