EasyManua.ls Logo

Siemens Cerberus CS1140 - Allocations; Interactive and Analogplus Devices (after Localization)

Siemens Cerberus CS1140
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e1249d2
38
Fire & Security Products
Siemens Building Technologies Group
01.1999
Enter localization index in the commissioning list / ground plan or register in
the SmartHandy
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 203 (1601,426)
>001.001.001.001/001: DOT1131 (1501,427)
>001.001.001.002/001: DOT1131 (1501,428)
>001.001.001.003/001: DOT1131 (1501,429)
>001.001.001.004/001: DOT1131 (1501,430)
001.001.002/ZO multi/2/laboratory 201 (1602,445)
>001.001.002.001/004: DO1131 (1501,446)
>001.001.002.002/004: DO1131 (1501,447)
2
3
AI
4
Window
Door
5
1
6
laboratory 201
corridor 200
office office office
laboratory 203
laboratory 205
office office office
1
2
3
5
4
211209207
206204202
7
8
910
$4
2nd floor west
laboratory 201
or
$5
(Functional characteristics of the
SmartHandy see document e1689)
001: DO1131
002: DO1131
003: DO1131
004: DO1131
Repeat the procedure until all required devices have been localized
Deactivate address allocation ( page 93)
4.5 Allocations
Devices, lines, and inputs/outputs of the physical structure are linked with the corre-
sponding elements of the logical structure using the SWE11. In the case of interactive and
AnalogPLUS devices, the localization data (bus address and, in the case of interactive
devices, the ID number) are also allocated.
4.5.1 Interactive and AnalogPLUS devices (after localization)
Principle
Building layouts/logical connections (logical structure) and hardware configuration
(physical structure) are produced by the SWE11. The lowest levels of both of these struc-
tures – logical elements and physical devices – are linked to one another.
During address allocation, the location data on the CC/CI11 main control unit are also
registered in the form of a tree structure. This structure corresponds to the physical ar-
rangement of the installed hardware, but contains only the data necessary for location,
i.e.: bus addresses, ID numbers (interactive devices only), device models, address al-
location localization indexes.
Using the SWE11, the localization structure data must be assigned to the devices of the
physical structure/elements of the logical structure that have already been linked. The
reference for assignment is the address allocation localization index or the device ID (in-
teractive devices only).

Table of Contents

Other manuals for Siemens Cerberus CS1140

Related product manuals