Fire & Security Products
Siemens Building Technologies Group
01.1999
Output module DC1154
(if input and output sections are used separately)
For details of procedure for manual allocation see page 42
Devices which have more than one D-Bus address, cannot be allocated with the func-
tion Auto link.
Devices with more than one bus address nevertheless only have one localization index
in the localization structure. Such devices must be assigned manually.
The following devices have more than one bus address:
T-branch module DC1135
For details of procedure for manual allocation see page 50
Output module DC1136
For details of procedure for manual allocation see page 54
4.5.3 Manual allocation of interactive devices
Automatic detectors and manual call points
Procedure(using the DO1151 detector as an example)
1. Switchover from the physical structure to the localization structure
Function Loc. Commissioning
2. Select an automatic detector or manual call point in the localization structure and the
corresponding element in the logical structure using the commissioning list
Reference:
Localization index of address programming or
device identification
select
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1151 4 (1501,427)
>001.001.001.002/001: DO1151 2 AI (1501,428)
>001.001.001.003/001: DO1151 (1501,429)
>001.001.001.004/001: DO1151 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1151 6 Window (1501,446)
>001.001.002.002/004: DOT1151 5 Door (1501,447)
3. Link nodes together
Function Structure Link
Logical element, physical de-
vice (not visible at the mo-
ment) and device in the local-
ization structure are identified
as localized
no prefix