’Collective’ input module DC1151
Procedure
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1151 input module in the localization struc-
ture and the corresponding element in the logical structure
Permissible element types:
– Collective detector element 1 (’EL col. det. 1’)
– Collective detector element 2 (’EL col. det. 2’)
– Collective detector element 3 (’EL col. det. 3’)
– Collective manual call point element (’EL DS11c/MS9i man’)
Reference:
Localization index of address allocation or
device identification
3. Link nodes together
Function Structure Link
select
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1151 4 (1501,427)
>001.001.001.002/001: DO1151 2 AI (1501,428)
>001.001.001.003/001: DO1151 (1501,429)
>001.001.001.004/001: DO1151 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1151 6 Window (1501,446)
>001.001.002.002/004: DOT1151 5 Door (1501,447)
Output module DC1154/DC1154-AA
Possible Uses
The output module DC1154 consists of a digital output section and a digital input section.
These may be used independently of one another. In the physical structure they are rep-
resented as individual devices on an interactive line (’out’ and ’in’). Depending on the ap-
plication, the two physical devices are linked with the same or two different logical ele-
ments.
Procedure to be adopted if the input section is used as confirmation path for out-
put section
Normal situation
Element type to be used: ’Output element with confirmation path (’EL out 2’)