DC1154 is repre-
sented in the physical
structure by 2 individual
devices (out / in)
’EL out 2’
’DE DS11i out’’DE DS11i in’
Logical
structure
Physical
structure
Links
Function unit
Localization
structure
’150: DC1154’
DC1154 is represented
in the localization structure
by one device
Station
SWE11:
SWE11:
Function unit
Zone
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1154 output module in the localization
structure and the corresponding ’output element with confirmation’ (’EL out 2’) in the
logical structure
Reference:
Localization index of address allocation or
device identification
3. Link nodes together
Function Structure Link
SWE11 takes over the same localization data (Bus-address, ID-number) auto-
matically in both devices linked to the element