Procedure to be adopted if the input section and output section are used sepa-
rately
The two physical devices are linked to two different logical elements
Types of element to be used for the output section:
– Output element without confirmation (’EL out 1’) or
– Element remote transmission channel (’EL RT ch.’)
and for the input section:
– Digital element (’EL digital’) or
– Digital detector element (’EL digital det.’) or
– Digital manual call point element (’EL digital man.’) or
– Command element (’EL command’)
DC1154 is repre-
sented in the physical
structure by 2 individual
devices (out / in)
’EL out 1’
’DE DS11i in’’DE DS11i out’
Zone
Localization
structure
’150: DC1154’
Function unit
DC1154 is represented
in the localization structure
by one device
e.g. ’EL digital
det.’
Zone
Logical
structure
Physical
structure
Links
’FU DS11i’
Station
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1154 output module in the localization
structure and the first of the corresponding elements in the logical structure, e.g. the
’output element without confirmation’ (’EL out 1’) linked to the output section