e1249d1
14
Fire & Security Products
Siemens Building Technologies Group
01.1999
3.4.14 Control module «Contacts» E3G050
Pos. Component Preparation Default
1 DIL switch S3
I-Bus address
Set according to system documentation address 0
2 Maintenance switch S2
Activate test LEDs
Set to ON for commissioning Set to OFF
2
Test LEDs
1
3.4.15 Control module «monitored» E3G060
Pos. Component Preparation Default
1 DIL switch S3
I-Bus address
Set according to system docu-
mentation
address 0
2 DIL switch S6-1...6
Assign ”emergency alarm” activation
Set as per system documentation Set to ”off” (= even if ”emer-
gency alarm” activated)
3 Maintenance switch S2
Activate test LEDs
Set to ON for commissioning Set to OFF
Test LEDs
3
1
2