e1249d2
50
Fire & Security Products
Siemens Building Technologies Group
01.1999
Input module DC1131/DC1131-AA
Procedure
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1131 input module in the localization struc-
ture and the corresponding element in the logical structure
Permissible element types:
– ’Digital element’ (’EL digital’)
– ’Digital detector element’ (’EL digital det.’)
– ’Digital manual call point element’ (’EL digital man.’)
– ’Command element’ (’EL command’)
– ’Output element with confirmation’ (’EL out 2’) as confirmation path only
’EL out 2’ see ’Restriction’ page 49
Reference:
Localization index of the address allocation
select
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1131 4 (1501,427)
>001.001.001.002/001: DO1131 2 AI (1501,428)
>001.001.001.003/001: DO1131 (1501,429)
>001.001.001.004/001: DO1131 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1131 6 Window (1501,446)
>001.001.002.002/004: DOT1131 5 Door (1501,447)
3. Link nodes together
Function Structure Link
Output module DC1134/DC1134-AA
Procedure
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1134 output module in the localization
structure and the corresponding element in the logical structure
Permissible element types:
Output element without confirmation (’EL out 1’)
– Output element with confirmation (’EL out 2’) as output path only
’EL out 2’ see ’Restriction’ page 49
– Remote transmission channel element (”EL RT ch”)
Reference:
Localization index of the address allocation
select
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1131 4 (1501,427)
>001.001.001.002/001: DO1131 2 AI (1501,428)
>001.001.001.003/001: DO1131 (1501,429)
>001.001.001.004/001: DO1131 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1131 6 Window (1501,446)
>001.001.002.002/004: DOT1131 5 Door (1501,447)
3. Link nodes together
Function Structure Link