Input / output module DC1192
Possible Uses
The DC1192 input / output module can either be used as an input module for the opera-
tion of a collective line (DC1192c) or as an output module for the activation of supervised
alarm devices (DC1192h).
Procedure when used as an input module
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1192c input module in the localization struc-
ture and the corresponding element in the logical structure
Permissible element types:
Collective detector element 1 (’EL col. det. 1’)
Collective detector element 2 (’EL col. det. 2’)
Collective detector element 3 (’EL col. det. 3’)
– Collective manual call point element (’EL DS11c/MS9i man’)
Reference:
Localization index of the address allocation
3. Link nodes together
Function Structure Link
select
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1151 4 (1501,427)
>001.001.001.002/001: DO1151 2 AI (1501,428)
>001.001.001.003/001: DO1151 (1501,429)
>001.001.001.004/001: DO1151 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1151 6 Window (1501,446)
>001.001.002.002/004: DOT1151 5 Door (1501,447)
Procedure when used as an output module
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1192h output module in the localization
structure and the corresponding element in the logical structure
Permissible element types:
Element alarm horn (’EL Al horn’)
– Element supervised (’EL superv.’)
– Element internal horn (’EL int. horn’)
– Element external horn (’EL ext. horn’)
Reference:
Localization index of the address allocation
3. Link nodes together
Function Structure Link
select
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1151 4 (1501,427)
>001.001.001.002/001: DO1151 2 AI (1501,428)
>001.001.001.003/001: DO1151 (1501,429)
>001.001.001.004/001: DO1151 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1151 6 Window (1501,446)
>001.001.002.002/004: DOT1151 5 Door (1501,447)