67
Fire & Security Products
Siemens Building Technologies Group
01.1999
Logical
structure
Physical
structure
Function unit
’FU LON’
Device
Station
’ST CC11’
’DE LON 2’
No link with the
logical structure!
LON-Bus address
Mimic display control unit K3R071 / parallel display panel B3R051
The mimic display control unit / parallel display panel is only represented in the physical
structure. There is no link with the logical structure:
Logical
structure
Physical
structure
Function unit
’FU LON’
Devices
Station
’ST CC11’
’DE LON 1’
No link with the
logical structure!
Each ’DE LON 1’ device node represents a single mimic display control unit/parallel
display panel connected to the LON/mimic display card K3I050. Each device node
represents an eighth of a LON/ K3I050 mimic display card.
Each of the maximum of 8 LON’s/mimic display cards has the same D-Bus address
but a different panel address.
LON-Bus address
Device addresses (1..8)