Link-up and update
8.3 Time monitoring
CPU 410-5H Process Automation/CPU 410 SMART
112 System Manual, 10/2013, A5E32631667-AA
Figure 8-1 Meanings of the times relevant for updates
Response to time-outs
If one of the times monitored exceeds the configured maximum value, the following
procedure is started:
1. Cancel update
2. Fault-tolerant system remains in standalone mode, with the previous master CPU in RUN
3. Cause of cancelation is entered in diagnostic buffer
4. Call OB 72 (with corresponding start information)
The standby CPU then reevaluates its system data blocks.
Following this, after at least one minute, the CPU tries again to perform the link-up and
update. If still unsuccessful after a total of 10 retries, the CPU abandons the attempt. You
yourself will then need to start the link-up and update again.
A monitoring timeout can be caused by:
High interrupt load (e.g. from I/O modules)
High communication load causing prolonged execution times for active functions
In the final update phase, the system needs to copy large amounts of data to the
standby CPU.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 410-5H Process Automation and is the answer not in the manual?

Siemens CPU 410-5H Process Automation Specifications

General IconGeneral
BrandSiemens
ModelCPU 410-5H Process Automation
CategoryController
LanguageEnglish

Related product manuals