System modifications during redundant operation   
10.6 Re-parameterization of a module 
  CPU 410-5H Process Automation/CPU 410 SMART 
162  System Manual, 10/2013, A5E32631667-AA 
 
Note 
After changing the hardware configurat
ion, download takes place practically automatically. 
This means that you no longer need to perform the steps described in sections 
Step 2: 
 (Page 162) to Step 5: Transition to redundant system mode 
 164). The system behavior remains as described. 
re information in the HW Config online help "Download to module -> 
Download station configuration in RUN mode".
 
 
 
Step 1: Editing parameters offline 
Starting situation 
The fault-tolerant system is operating in redundant system mode. 
1.  Edit the module parameters offline in HW Config. 
2.  Compile the new hardware configuration, but do 
 load it into the target system just yet. 
The modified hardware configuration is in the PG/ES. The target system continues operation 
with the old configuration in redundant system mode. 
 
Step 2: Stopping the reserve CPU 
Starting situation 
The fault-tolerant system is operating in redundant system mode. 
1.  For CPU access protection with password: In SIMATIC Manager, select a CPU of the 
fault-tolerant system, then select 
"PLC > Access Rights > Setup" from the menu. Enter the CPU access password. 
2.  In SIMATIC Manager, select a CPU of the fault-tolerant system, then select "PLC > 
Operating Mode" from the menu. 
3.  In the "Operating Mode" dialog box, select the standby CPU and click "Stop".