Supplementary information
16.10 Communication via fault-tolerant S7 connections
CPU 410-5H Process Automation/CPU 410 SMART
246 System Manual, 10/2013, A5E32631667-AA
16.10
Communication via fault-tolerant S7 connections
Availability of communicating systems
Fault-tolerant communication expands the overall SIMATIC system by additional, redundant
communication components such as CPs and bus cables. To illustrate the actual availability
of communicating systems when using an optical or electrical network, a description is given
below of the possibilities for communication redundancy.
Requirement
The essential requirement for the configuration of fault-tolerant connections with STEP 7 is a
configured hardware installation.
The hardware configuration in both subsystems of a fault-tolerant system
must
be identical.
This applies in particular to the slots.
Depending on the network used, CPs can be used for fault-tolerant and fail-safe
communication, see Appendix Function and communication modules that can be used in a
redundant configuration (Page 305)
Industrial Ethernet with ISO protocol or PROFIBUS without distributed I/O and, as of Version
6.0, ISO on TCP is supported. Fault-tolerant S7 connections via Industrial Ethernet with ISO
on TCP are supported by the integrated PN interface and corresponding CPs. You require a
suitable CP for fault-tolerant S7 connections via Industrial Ethernet with ISO protocol or via
PROFIBUS. These connections are not possible via the internal PROFIBUS-DP interface.
Only Industrial Ethernet is supported for connecting to PC stations using fault-tolerant S7
connections. To be able to use fault-tolerant S7 connections between a fault-tolerant system
and a PC, you must install the "S7-REDCONNECT" software package on the PC. The
software is part of the SIMATIC Net CD. Communication via ISO on TCP is also supported
as of version 8.1.2. Please refer to the product information on the SIMATIC NET PC
software to learn more about the CPs you can use at the PC end.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 410-5H Process Automation and is the answer not in the manual?

Siemens CPU 410-5H Process Automation Specifications

General IconGeneral
BrandSiemens
ModelCPU 410-5H Process Automation
CategoryController
LanguageEnglish

Related product manuals