I/O configuration variants   
4.6 System and media redundancy at the PROFINET IO interface 
  CPU 410-5H Process Automation/CPU 410 SMART 
64  System Manual, 10/2013, A5E32631667-AA 
The figure below shows the view in STEP 7, the logical view and the physical view of the 
configuration with two integrated IO devices in system redundancy. Note that the view in 
STEP 7 does not exactly match the physical view. 
 
Figure 4-12  System redundancy in different views 
Commissioning a system-redundant configuration 
It is imperative that you assign unique names during commissioning. 
Proceed as follows when you change or reload a project: 
1.  Set the fault-tolerant system to STOP on both sides. 
2.  Reset the standby CPU memory.