206/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 28 Parameter level 25.09.2013
F
and
A
and
or
P
Vhsmin%
Bild 139/0807
Press
or to change the value as
required.
Example: 00.0
F
or
A
P
Vhmins%
Bild 140/0707
Release
F
or
A
.
The required value is adopted.
Example: P5:50.0:46.0
>3 s
P
Vh
mi n
s%
Bild 124/0707
Keep depressed for >3 s.
CALC appears.
P
Vhmins%
Bild 141/0707
The display jumps to P6.
All curvepoints from P5 to P9 have now been
automatically recalculated (linear interpolation):
Curvepoint Value 1
fuel
Value 2
air
P5
50.0 46.0
P6
57.5 57.0
P7
65.0 68.0
P8
72.0 79.0
P9
80.0 90.0
>3 s
P
Vh
mi n
s%
Bild 124/0707
Keep depressed for >3 s.
CALC appears.
P
Vhmins%
Bild 142/0707
The display jumps to P4.
All curvepoints from P1 to P5 have now been
automatically recalculated (linear interpolation):
Curvepoint Value 1
fuel
Value 2
air
P5
50.0 46.0
P4
45.5 40.0
P3
41.0 35.0
P2
36.5 29.5
P1
32.0 24.0

Table of Contents