Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 28 Parameter level 25.09.2013
>3 s
P
Vh
mi n
s%
Bild 124/0707
>3 s
If it is not only the current curvepoint that shall be changed, but all other points in the direction of travel as
well, a new straight line from the current point to P9 (press
) or P1 (press ) can be calculated by
a long push on
or .
Display CALC
Example of presentation
)
P5 down to P1
Keep
depressed for >3 s
P5 up to P9
Keep
depressed for >3 s
CALC -
CALC +
Figure 100: Changing several curvepoints
Note
Due to interpolation, a number of curvepoints change. The curvepoints
changed must be approached while using the warm settings to be able to
make a check on the burner. If these points have not yet been completely
approached, the normal display of the AZL2... shows OFF UPr 0 / OFF
UPr1.