216/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
Setting values
0 = 9600
1 = 19200
147 Setting of parity for Modbus communication
Setting value
0 = none
1 = odd
2 = even
1 Selection Edit 0 2 1 0 SO
148 Default output if communication with building automation is interrupted
Setting values
For
modulation operation the setting range is as follows:
0…19.9 = burner off
20…100 = 20…100% burner rating
For
multistage operation apply to setting range:
0 = burner OFF, P1, P2, P3
Invalid = no default output predefined by building automation
Default setting:
Invalid
1 Output Edit / clear 0% 100% 0.1% undefined SO (BA)
149 Fuel 1: Default output if communication with building automation is
interrupted
Setting values
For
modulation operation the setting range is as follows:
0…19.9 = burner off
20…100 = 20…100% burner rating
For
multistage operation apply to setting range:
0 = burner OFF, P1, P2, P3
Invalid = no default output predefined by building automation
Default setting:
Invalid
1 Output Edit / clear 0% 100% 0.1% undefined SO (BA)
161 Number of faults 1 Std_u16 Read only 0 65535 1 0 Info / Service
162 Operating hours resettable 1 Std_s32 Reset 0 h 9999999 h 1 h 0 h Info / Service