220/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
236 Gas: Pressure switch-min input
0 = inactive
1 = pressure switch-min (before fuel valve 1 (V1))
2 = valve proving via pressure switch-min (between fuel valve 1 (V1)
and fuel valve 2 (V2))
1 Selection Edit 1 2 1 1 SO
237 Gas: Pressure switch-max / POC input
0 = inactive
1 = pressure switch-max
2 = POC
3 = Pressure switch valve proving
1 Selection Edit 1 3 1 1 SO
239 Gas. Forced intermittent operation
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 SO
240 Repetition limit loss of flame
1 = no repetition
2 = 1 repetition
1 Std_u8 Edit 1 2 1 1 OEM
241 Gas: Execution valve proving
0 = no valve proving
1 = valve proving on startup
2 = valve proving on shutdown
3 = valve proving on startup and shutdown
1 Selection Edit 0 3 1 0 SO
242 Gas: Valve proving evacuation time 1 Time Edit 0.2 s 10 s 0.2 s 3 s OEM
243 Gas: Valve proving time test atmospheric pressure 1 Time Edit 0.2 s 60 s 0.2 s 10 s OEM
244 Gas: Valve proving filling time 1 Time Edit 0.2 s 10 s 0.2 s 3 s OEM
245 Gas: Valve proving time test gas pressure 1 Time Edit 0.2 s 60 s 0.2 s 10 s OEM
246 Gas: Waiting time gas shortage 1 Time Edit 0.2 s 60 s 0.2 s 10 s OEM
248 Gas: Postpurge time (t3) (abortion if load controller On) 1 Time Edit 1 s 108 min 0.2 s 1 s SO
261 Oil: Active detector of flame evaluation
0 = QRB
1 = ION / QRA
1 Selection Edit 0 1 1 0 SO
262 Oil: Prepurging
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 OEM
265 Oil: Prepurge time 1 Time Edit 5 s 60 min 0.2 s 30 s SO
266 Oil: Preignition time 1 Time Edit 0.6 s 60 min 0,2 s 2 s SO