Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
267 Oil: Safety time 1 (TSA1) 1 Time Edit 1 s 15 s 0,2 s 5 s OEM
269 Oil: Time to respond to pressure faults within safety time 1 (TSA1)
and safety time 2 (TSA2)
1 Time Edit 0.4 s 14.6 s 0,2 s 1,8 s OEM
270 Oil: Interval 1 1 Time Edit 0.4 s 60 min 0,2 s 2 s SO
271 Oil: Safety time 2 (TSA2) 1 Time Edit 1 s 15 s 0,2 s 10 s OEM
272 Oil: Interval 2 1 Time Edit 0.4 s 60 min 0,2 s 2 s SO
273 Oil: Afterburn time 1 Time Edit 0.2 s 60 s 0.2 s 8 s SO
274 Oil: Postpurge time (no extraneous light test) 1 Time Edit 0.2 s 108 min 0.2 s 15 s SO
276 Oil: Pressure switch-min input
0 = inactive
1 = active from phase 38
2 = active from safety time (TSA)
1 Selection Edit 1 2 1 1 SO
277 Oil: Pressure switch-max/POC input
0 = inactive
1 = pressure switch-max
2 = POC
1 Selection Edit 1 2 1 1 SO
279 Oil: Forced intermittent operation
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 SO
280 Repetition limit value loss of flame
1 = no repetition
2 = 1 repetition
1 Std_u8 Edit 1 2 1 2 OEM
281 Oil: Point in time oil is ignited
0 = short preignition (Ph38)
1 = long preignition (with fan) (Ph22)
1 Selection Edit 0 1 1 0 SO
284 Oil: Postpurge time 3 (abortion if load controller On) 1 Time Edit 1 s 108 min 0.2 s 1 s SO
285 Oil: gas pressure switch-min with «Lo Gp»
0 = inactive
1 = active
1 Selection Edit 0 1 1 0 SO
300 Basic unit
301 Fuel 1: Burner operating mode (fuel train, modulating / multistage,
actuators, etc.)
-- = undefined (delete curves)
1 = G mod
1 Selection Edit / clear 1 27 1 Undefined SO