223/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
2...15 = number of repetitions
16 = constant repetition
325 Fuel 1 gas: Prepurge time 1 Time Edit 5 s 60 min 0.2 s 30 s SO
326 Fuel 1 gas: Preignition time 1 Time Edit 0.4 s 60 min 0.2 s 2 s SO
327 Fuel 1 gas: Safety time 1 (TSA1) 1 Time Edit 1 s 10 s 0.2 s 5 s OEM
329 Fuel 1 gas: Time to respond to pressure faults within safety time 1
(TSA1) and safety time 2 (TSA2)
1 Time Edit 0.4 s 9.6 s 0.2 s 1.8 s OEM
330 Fuel 1 gas: Interval 1 1 Time Edit 0.4 s 60 s 0.2 s 2 s SO
331 Fuel 1 gas: Safety time 2 (TSA2) 1 Time Edit 1 s 10 s 0.2 s 7 s OEM
332 Fuel 1 gas: Interval 2 1 Time Edit 0.4 s 60 s 0.2 s 2 s SO
333 Fuel 1 gas: Afterburn time 1 Time Edit 0.2 s 60 s 0.2 s 8 s SO
334 Fuel 1 gas: Postpurge time (no extraneous light test) 1 Time Edit 0.2 s 108 min 0.2 s 15 s SO
335 Gas: Air pressure switch (LP)
0 = inactive
1 = active
2 = active, except phase 60...66 (pneumatic operation only)
1 Selection Edit 1 2 1 1 SO
336 Fuel 1 gas: Pressure switch-min input
0 = inactive
1 = pressure switch-min (before fuel valve 1 (V1))
2 = valve proving via pressure switch-min (between fuel valve 1 (V1)
and fuel valve 2 (V2))
1 Selection Edit 1 2 1 1 SO
337 Fuel 1 gas: Pressure switch-max / POC input
0 = inactive
1 = Pressure switch-max
2 = POC
1 Selection Edit 1 3 1 2 SO
339 Fuel 1 gas. Forced intermittent operation
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 SO
340 Repetition limit value loss of flame
1 = no repetition
2 = 1 repetition
1 Std_u8 Edit 1 2 1 1 OEM
341 Fuel 1 gas: Execution valve proving
0 = no valve proving
1 = valve proving on startup
2 = valve proving on shutdown
1 Selection Edit 0 3 1 0 SO