Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
3 = valve proving on startup and shutdown
342 Fuel 1 gas: Valve proving evacuation time 1 Time Edit 0.2 s 10 s 0.2 s 3 s OEM
343 Fuel 1 gas: Valve proving time test atmospheric pressure 1 Time Edit 0.2 s 60 s 0.2 s 10 s OEM
344 Fuel 1 gas: Valve proving filling time 1 Time Edit 0.2 s 10 s 0.2 s 3 s OEM
345 Fuel 1 gas: Valve proving time test gas pressure 1 Time Edit 0.2 s 60 s 0.2 s 10 s OEM
346 Fuel 1 gas: Waiting time gas shortage 1 Time Edit 0.2 s 60 s 0.2 s 10 s OEM
348 Fuel 1 gas: Postpurge time (t3) (abortion if load controller ON) 1 Time Edit 1 s 108 min 0.2 s 1 s SO
361
Fuel 1 oil: Active detector of flame evaluation
0 = QRB
1 = ION / QRA
1 Selection Edit 0 1 1 1 SO
362
Fuel 1 oil: Prepurging
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 OEM
365 Fuel 1 oil: Prepurge time 1 Time Edit 5 s 60 min 0.2 s 30 s SO
366 Fuel 1 oil: Preignition time 1 Time Edit 0.6 s 60 min 0.2 s 2 s SO
367 Fuel 1 oil: Safety time 1 (TSA1) 1 Time Edit 1 s 15 s 0.2 s 5 s OEM
369
Fuel 1 oil: Time to respond to pressure faults within safety time 1
(TSA1) and safety time 2 (TSA2)
1 Time Edit 0.4 s 14.6 s 0.2 s 1.8 s OEM
370 Fuel 1 oil: Interval 1 1 Time Edit 0.4 s 60 min 0.2 s 2 s SO
371 Fuel 1 oil: Safety time 2 (TSA2) 1 Time Edit 1 s 15 s 0.2 s 10 s OEM
372 Fuel 1 oil: Interval 2 1 Time Edit 0.4 s 60 min 0.2 s 2 s SO
373 Fuel 1 oil: Afterburn time 1 Time Edit 0.2 s 60 s 0.2 s 8 s SO
374 Fuel 1 oil: Postpurge time (no extraneous light test) 1 Time Edit 0.2 s 108 min 0.2 s 15 s SO
376
Fuel 1 oil: Pressure switch-min input
0 = inactive
1 = active from phase 38
2 = active from safety time (TSA)
1 Selection Edit 1 2 1 1 SO
377
Fuel 1 oil: Pressure switch-max / POC input
0 = inactive
1 = pressure switch-max
2 = POC
1 Selection Edit 1 2 1 1 SO
379
Fuel 1 oil: Forced intermittent operation
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 SO