225/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
380
Repetition limit value loss of flame
1 = no repetition
2 = 1 repetition
1 Std_u8 Edit 1 2 1 1 OEM
381
Fuel 1 oil: Point in time oil is ignited
0 = short preignition (Ph38)
1 = long preignition (with fan) (Ph22)
1 Selection Edit 0 1 1 0 SO
384 Fuel 1 oil: Postpurge time 3 (abortion if load controller ON) 1 Time Edit 1 s 108 min 0.2 s 1 s SO
385 Fuel 1 oil: gas pressure switch-min with «Lo Gp»
0 = inactive
1 = active
1 Selection Edit 0 1 1 0 SO
400 Ratio curves
401 Ratio control curves fuel actuator (curve setting only) 13 Std_s16 Edit 0 ° 90 ° 0.1 ° 0 °; 0 °; 15 °; undefined SO
402 Ratio control curves air actuator (curve setting only) 13 Std_s16 Edit 0 ° 90 ° 0.1 ° 0 °; 90 °; 45 °; undefined SO
403 Ratio control curves VSD (curve setting only) 13 Std_s16 Edit 15 % 100% 0.1% 0%; 100%; 50%;
undefined
SO
404 Fuel 1: Ratio control curves fuel actuator (curve setting only) 13 Std_s16 Edit 90° 0.1° 0°, 0°, 15°, undefined SO
405 Fuel 1: Ratio control curves air actuator (curve setting only) 13 Std_s16 Edit 90° 0.1° 0°, 90°, 45°, undefined SO
406 Fuel 1: Ratio control curves VSD (curve setting only) 13 Std_s16 Edit 15 % 100 % 0.1 % 0 %, 100 %, 50 %,
undefined
SO
500 Ratio control
501 No-flame positions fuel actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16 Edit 0 ° 90 ° 0.1 ° Index
0
1
2
Value
15°
SO
502 No-flame positions air actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16 Edit 0 ° 90 ° 0.1 ° Index
0
1
2
Value
90°
45°
SO
503 No-flame speeds VSD
Index 0 = no-load speed
Index 1 = prepurge speed
Index 2 = postpurge speed
3 Std_s16 Edit 0% 100% 0.1% Index
0
1
2
Value
0%
100%
50%
SO

Table of Contents