Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
504 Fuel 1: No-flame position fuel actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16 Edit 90° 0.1° 0°, 0°, 15° SO
505 Fuel 1: No-flame position air actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16 Edit 90° 0.1° 0°, 90°, 45° SO
506 Fuel 1: No-flame speed VSD
Index 0 = no-load speed
Index 1 = prepurge speed
Index 2 = postpurge speed
3 Std_s16 Edit 0 % 100 % 0.1 % 0 %, 100 %, 50 % SO
522 Ramp up 1 Std_u8 Edit 5 s 40 s 1 s 10 s SO
523 Ramp down 1 Std_u8 Edit 5 s 40 s 1 s 10 s SO
542 Activation of VSD / PWM fan
0 = inactive
1 = active
1 Selection Edit 0 1 1 0 SO
544 Ramp modulating 1 Std_u8 Edit 32 s 80 s 1 s 32 s SO
545 Lower output limit
undefined = 20 %
1 Output Edit / clear 20% 100% 0.1% undefined SO (BA)
546 Upper output limit
undefined = 100 %
1 Output Edit / clear 20% 100% 0.1% undefined SO (BA)
565 Fuel 1: Lower output limit
undefined = 20 %
1 Output Edit 20 % 100 % 0.1 % Undefined SO (BA)
566 Fuel 1: Upper output limit
undefined = 100 %
1 Output Edit 20 % 100 % 0.1 % Undefined SO (BA)
600 Actuators
601 Selection of reference point
Index 0 = fuel
Index 1 = air
0 = closed (<0°)
1 = open (>90°)
2 Selection Edit 0 1 1 Index
0
1
Value
1
0
SO
Password level
write: OEM
602 Actuator's direction of rotation
Index 0 = fuel
2 Selection Edit 0 1 1 Index
0
Wert
0
SO
Password level