227/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
Index 1 = air
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
1 0 write: OEM
606 Tolerance limit of position monitoring [0.1°]
Index 0 = fuel
Index 1 = air
Greatest position error where a fault is securely detected
error detection band: (P606-0.6°) to P606
2 Std_u8 Edit 0.5 ° 4° 0,1° Index
0
1
Value
1.7°
1.7°
SO
Password level
write: OEM
608 Fuel 1: Selection of reference point
0 = closed (<0°)
1 = open (>90°)
1 Std_u8 Edit 0 1 1 1 OEM
609 Fuel 1: Actuator's direction of rotation
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
1 Std_u8 Edit 0 1 1 0 OEM
610 Fuel 1: Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
Index 1 = air
Greatest position error where an error is securely detected
Error detection band: (parameter 606 -0.6°) up to parameter 606
1 Std_u8 Edit 0° 4° 0.1° 1.7° SO
611 Type of reference
Index 0 = fuel
Index 1 = air
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1…)
3 = both
2 Std_u8 Edit 0 3 1 Index
0
1
Value
0
0
SO
Password level
write: OEM
612 Fuel 1: Type of reference for fuel actuator
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1…)
3 = both
1 Std_u8 Edit 0 3 1 0 OEM
613 Type of actuator
Index 0 = fuel
Index 1 = air
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (6 Nm)
2 = 17 s / 90° (10 Nm)
2 Std_u8 Edit 0 2 1 0; 0 SO
Password level
write: OEM