Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
614 Fuel 1: Type of actuator
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (SQM33.6)
2 = 17 s / 90° (SQM33.7)
2 Std_u8 Edit 0 2 1 0; 0 SO
Password level
write: OEM
641 Control of speed standardization of VSD
Error diagnostics of negative values (refer to error code 82)
0 = no speed standardization
1 = speed standardization active
1 Std_s8 Edit -25 1 1 0 SO
642 Standardized speed
Index 0 = speed 1
Index 1 = speed 2 (internal monitoring)
2 Std_u16 Read only 650 6500 0.1 undefined SO
645 Configuration of analog output
0 = DC 0...10 V
1 = DC 2...10 V
2 = DC 0/2...10 V
1 Std_u8 Edit 0 2 1 0 SO
652 VSD behavior when safety loop / burner flange is open
0 = no VSD control when safety loop / burner flange is open
1 = VSD control independent of safety loop / burner flange
1 Std_u8 Edit 0 1 1 1 SO
653 VSD standstill supervision in standby mode
0 = deactivate
1 = active
1 Std_u8 Edit 0 1 1 1 SO
700 Error history
701 Error history: 701-725.01.Code 25 Std_u8 Read only 0 255 1 0 Info / Service
• Error history: 701-725.02.Diagnostic code 25 Std_u8 Read only 0 255 1 0 Info / Service
• Error history: 701-725.03.Error class 25 Std_u8 Read only 0 6 1 0 Info / Service
• Error history: 701-725.04.Phase 25 Std_u8 Read only 0 255 1 0 Info / Service
• Error history: 701-725.05.Startup counter 25 Std_s32 Read only 0 99999999 1 0 Info / Service
• Error history: 701-725.06.Output 25 Output Read only 0% 100% 0.1% 0% Info / Service
725 Error history: 701-725.07.Fuel 25 Std_u8 Read only 0 255 1 0 Info / Service
900 Process data
903 Current output
Index 0 = fuel
2 Output Read only 0% 100% 0.1% 0% Info / Service