Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
Bit 4 = 16: Fuel valve 2
Bit 5 = 32: Fuel valve 3 / pilot valve
951 Mains voltage (normalized)
AC 230 V: Voltage = value x 1.683
AC 120 V: Voltage = value x 0.843
1 Std_u8 Read only 0 V 255 V 1 V 0 V SO
954 Intensity of flame 1 Std_u8 Read only 0% 100% 1% 0% Info / Service
960 Actual flow rate (m³/h, l/h, ft³/h, gal/h) 1 Std_u16 Read only 0 6553.5 0.1 0 Info / Service
961 Phase (state for external module and display) 1 Std_u8 Read only 0 255 1 0 Info / Service
981 Error memory: Code 1 Std_u8 Read only 0 255 1 0 Info / Service
982 Error memory: Diagnostic code 1 Std_u8 Read only 0 255 1 0 Info / Service
992 Error flags 10 Hex_32 Reset 0 0xFFFFFFFF 1 0 SO
Legend
Std_u8 8 bit integer, not signed
Std_u16 16 bit integer, not signed
Std_u32 32 bit integer, not signed
Std_s8 8 bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of -1!
Std_s16 16 Bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of -1!
Std_s32 32 Bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of -1!