Menus in the WBM
5.1 The System menu
SCALANCE X-200
66 Configuration Manual, 03/2015, C79000-G8976-C285-06
Modify C-PLUG, Modify button
If you are logged on as administrator, you can make settings here.
Copy internal Configuration to C-PLUG and Restart
The configuration in the internal flash memory of the switch is copied to the C-PLUG and
this is followed by a restart.
Use case:
The X-200 IE switch starts up with a C-PLUG inserted. This contains a configuration that
differs from the IE Switch X-200 or a configuration containing errors. With this function,
you can overwrite the content of the C-PLUG with the original device configuration.
Copy default Configuration to C-PLUG and Restart
This stores the configuration with all factory default values on the C-PLUG. This is
followed by a restart during which the X-200 IE switch restarts with these default values.
Clean C-PLUG (Low Level Format, Configuration lost)
Deletes all data from the C-PLUG and triggers low-level formatting. This is not followed
by an automatic restart and the device displays an error. You can clear this error status
by restarting or removing the C-PLUG after turning off the basic device. To retain the
configuration of the basic device even after deleting the C-PLUG, the configuration data
stored on the C-PLUG is transferred to the internal memory of the basic device.
Continue without C-PLUG
If the C-PLUG is removed from a device, an error message is displayed after the device
restarts. In this case, you can select the "Continue without C-PLUG" option to change the
device to the mode without a C-PLUG.
Your selection is then adopted when you click "Modify".
Syntax of the Command Line Interface
Table 5- 10 C-PLUG Information - CLI\SYSTEM\C-PLUG>
Command
Description
Comment
info
Displays the current status (information) of the C-PLUG.
initdef Initializes the C-PLUG with the default parameters and restarts
the device.
Administrator only
initmem Initializes the C-PLUG with the MEMORY parameters and re-
starts the device.
Administrator only
usecplug [D] If the C-PLUG was removed, the next time you restart the de-
vice, an error command is displayed in the Command Line
Interface.
By entering the useplug D command, you can change the de-
vice to operate in the mode without C-PLUG.
Administrator only
clear
Erases the data on the C-PLUG.
Administrator only