Interrupts/diagnostic alarms
14.4 Diagnostics response
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
131
The following table shows the parameter assignment for the example:
Table 14- 21 Parameter assignment
Parameter
Power quality analysis functions
Enable
Diagnostics power quality Enable
Determining the overcurrent
Enable
Nominal value current
2000 A
Threshold overcurrent
100%
In this example you define the Threshold overcurrent of 100%. This corresponds to a primary
current of 4000 A.
If the "Threshold overcurrent" is exceeded, the module sets Bit 4 "Overcurrent" for the phase
in the data record DS 160.
As long as the "Threshold overcurrent" is exceeded, the module reports the diagnostics
"Power quality" and the qualifier bit 7 is set.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals