Technical specifications
15.1 Technical specifications
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
137
Accuracy class according to IEC 61557-12
– Measured variable voltage
0,2
– Measured variable current
0,2
– Measured variable apparent power
0.5
– Measured variable active power
0.5
– Measured variable reactive power
1
– Measured variable power factor
0.5
– Measured variable active energy
0.5
– Measured variable reactive energy
1
– Measured variable neutral current
0,2
– Measured variable phase angle
±0.5 °; not covered by IEC 61557-12
– Measured variable frequency
0.05
– Measured variable harmonic
1
– Measured variable THDU
1
– Measured variable THDI
1
Accuracy class line analysis acc. to IEC 61000-4-
30
– Measured variable voltage
Class S
– Measured variable current
Class S
– Measured variable frequency
Class S
– Measured variable voltage interruption
Class S
– Measured variable voltage dip and
swell
Class S
– Measured variable harmonic voltage
Class S
– Measured variable harmonic current
Class S
Potential separation channels
• between the channels
No
• between the channels and backplane bus
Yes
• Between the channels and load voltage L+
Yes; Including FE
Isolation tested with Between channels and backplane bus, 24 V
supply: Routine test, 1 920 V AC, 2 s; between
backplane bus and 24 V supply: Type test, 707 V