Technical specifications
15.1 Technical specifications
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
136 Manual, 07/2018, A5E42674880-AA
Measuring inputs for voltage
– Measurable line voltage between phase
and neutral conductor
300 V
– Measurable line voltage between the
line conductors
519 V
– Measurable line voltage between phase
and neutral conductor, min.
3 V
– Measurable line voltage between phase
and neutral conductor, max.
300 V
– Measurable line voltage between the
line conductors, min.
6 V
– Measurable line voltage between the
line conductors, max.
519 V
– Measurement category for voltage
measurement in accordance with IEC
61010-2-030
CAT II
– Internal resistance line conductor and
neutral conductor
1.5 MΩ
– Power consumption per phase
60 mW; 300 V AC
– Impulse voltage resistance 1,2/50µs
2.5 kV
Measuring inputs for current
– measurable relative current (AC), min.
1 %; Relative to the secondary rated current 5 A
– measurable relative current (AC), max.
100 %; Relative to the secondary rated current 5
– Continuous current with AC, maximum
permissible
5 A; 6 A permanent thermal overload
– Apparent power consumption per
phase for measuring range 5 A
0.6 V·A
– Rated value short-time withstand cur-
rent restricted to 1 s
100 A
– Input resistance measuring range 0 to 5
A
25 mΩ; At the terminal
– Zero point suppression
0 ... 20%, referred to the nominal current
– Surge strength
10 A; for 1 minute