Parameter data records
A.2 Structure of the parameter data record 128 for the entire module
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
149
Figure A-8 Channel parameter block
Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
parameter data record 128.
Error code in STATUS parame-
ter
(hexadecimal)
Meaning
Solution
Byte 0
Byte 1
Byte 2
Byte 3
DF
80
B0
00
Number of the data record unknown
Enter a valid number for the data record.
DF 80 B1 01 Length of the data record incorrect Enter a valid value for the data record
length.
DF 80 B2 00 Slot invalid or cannot be accessed. Check the station whether the module is
plugged or drawn.
Check the assigned values for the pa-
rameters of the WRREC instruction
DF
80
E0
01
Incorrect version
Check Byte 0. Enter valid values.
DF 80 E0 02 Error in the header information Check bytes 1 to 3, 32, 33, 52, 53, 72
and 73. Correct the length and number of
the parameter blocks.