Parameter data records
A.2 Structure of the parameter data record 128 for the entire module
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
150 Manual, 07/2018, A5E42674880-AA
Error code in STATUS parame-
ter
(hexadecimal)
DF 80 E1 01 Reserved bits are not 0. Check bytes 8, 14, 15, 30, 31, 34, 42,
50...53, 54, 62, 70...73, 74, 82, 90...93
and set the reserved bits back to 0.
DF 80 E1 05 "Voltage measuring range" invalid Check Byte 5. Permitted values: 01
H
to
H
DF 80 E1 20 "Connection type" invalid Check Byte 4. Permitted values: 00
H
,
0B
H
... 01
H
DF 80 E1 21 "User data variant" not possible or input
data configuration not large enough
Check Byte 9. Select a different user data
variant or change the configuration.
DF 80 E1 22 "User data variant" invalid Check Byte 9. Select a valid code for the
Check Byte 6. Enter valid values.
DF 80 E1 29 "Tolerance factor overcurrent in relation to
nominal value current [0.1%]" invalid
Check bytes 35, 55 and 75. Enter valid
DF 80 E1 2A "Tolerance time overcurrent" invalid Check bytes 36...37, 56...57, 67...77.
DF 80 E1 2B "Low limit current measurement" in relation
to nominal value current [0.1%] invalid
Check bytes 43, 63 and 83. Enter valid
DF 80 E1 2C "Current transformer primary current [A]"
Check bytes 38...41, 58...61, 78...81.
DF 80 E1 2D "Voltage transformer primary voltage [V]"
Check bytes 46...49, 66...69, 66...69,
88...89. Enter valid values.
DF 80 E1 2E "Voltage transformer secondary voltage [V]"
invalid
Check bytes 38…42 with bytes 58…62
and bytes 78…82 and bytes 44…49 with
bytes 64…69 and bytes 84…89 for iden-
DF 80 E1 2F "End value energy meter" invalid Check Bit 4...6 in Byte 6. Enter valid val-
DF 80 E1 30 Invalid data record number. Check the data record number. Enter a
valid data record number.
DF 80 E1 3E Only for connection type 3P4W1 and
3P3W1.
Current or voltage transformer parameters
for the different phases are not identical.
Check bytes 38...42 with bytes 58...62
and bytes 78...82 as well as bytes 44...49
with bytes 64...69 and bytes 84...80 for
identical values.
Enter identical values for current trans-
former (secondary current, primary cur-
rent, direction of current) and voltage
transformer (secondary voltage, primary
voltage) at all three phases.
DF 80 E1 3F "End value for energy meter" or transmis-
sion ratio (primary value, secondary value)
of current and voltage too low.
Increase the end value of the energy
meter or the ratio of primary to secondary
current for current transformer and/or
primary to secondary voltage for voltage
DF 80 E1 43 "Current transformer secondary current" for
neutral or all three phases invalid
Check bits 4...5 in bytes 14, 42, 62, 82.