Parameter data records
A.2 Structure of the parameter data record 128 for the entire module
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
151
Error code in STATUS parame-
ter
(hexadecimal)
DF 80 E1 44 "Voltage dip limit value in relation to nomi-
nal value voltage [0.1%]" invalid
Check bytes 16...17. Enter valid values
(voltage dip limit value must be smaller
than the respective nominal voltage)
DF 80 E1 45 "Voltage swell limit value in relation to nom-
inal value voltage [0.1%]" invalid
Check bytes 20...23. Enter valid values
(voltage swell limit value must be greater
than the respective nominal voltage)
DF 80 E1 46 "Threshold overcurrent in relation to nomi-
nal value current [0.1%]" invalid
Check bytes 24...27. Enter valid values
(threshold overcurrent must be greater
DF 80 E1 47 "Number of cycles for analysis of voltage
Check bytes 28...29. Enter valid values.
DF 80 E1 49 Current transformer parameter for "residual
current analysis" invalid
Only with connection type 3P4W and
3P4WI and if neutral current is measured.
Current transformer primary current and
secondary current and direction of current
of the three phases must have identical
DF 80 E1 4 A Voltage transformer parameters for voltage
swell/dip invalid
Check the parameters secondary voltage,
primary voltage, nominal value voltage.
Enabled channels must have identical
DF 80 E1 4B Current transformer parameter for "Detect
overcurrent" invalid
Check the parameters secondary current,
primary current, nominal value current
and direction of current. Enabled chan-
nels must have identical parameters.
DF 80 E1 4C Parameters for determining the neutral
current invalid
Neutral current can only be determined
with connection type 3P4W and 3P4WI
Current transmission parameters primary
current, secondary current, nominal value
current and direction of current of the
three phases must be identical.
DF 80 E1 4D "Nominal value current [A]" invalid Check bytes 34...37, 66...69, 98...101.
DF 80 E1 4E "Nominal value voltage [V]" invalid Check bytes 50...53, 82...85, 114...117.
DF 80 E1 4F "Low limit current measurement in relation
to nominal value current [0.1%]" invalid
Check bytes 42...43, 74...75, 106...107.
DF 80 E1 50 The combination of "Nominal value voltage
[V]" and "Voltage dip limit value in relation
to nominal value voltage [0.1%]" invalid.
Select the permissible value in % so that
the secondary measuring voltage of 0 V
DF 80 E1 51 The combination of "Nominal value voltage
[V]" and "Voltage swell limit value in relation
to nominal value voltage [0.1%]" invalid.
Select the permissible value in % so that
the secondary measuring voltage of 300
DF 80 E1 52 The combination of "Nominal value current
[A]" and "Threshold overcurrent in relation
to nominal value current [0.1%]" invalid
Select the permissible value in % so that
the secondary measuring current of 6 A is