Parameter data records
A.2 Structure of the parameter data record 128 for the entire module
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
152 Manual, 07/2018, A5E42674880-AA
Error code in STATUS parame-
ter
(hexadecimal)
DF 80 E1 53 The combination of "Nominal value current
[A]" and "Tolerance factor overcurrent in
relation to nominal value current [0.1%]"
invalid
Select the permissible value in % so that
the secondary measuring current of 6 A is
not exceeded.
DF 80 E1 54 The combination of "Nominal value voltage
[V]" and "Tolerance factor overvolt-
age/undervoltage in relation to nominal
value voltage [0.1%]" lies outside the per-
Select the permissible value in % so that
the secondary measuring voltage of 300
V is not exceeded.
DF 80 E1 55 "Nominal value current [A]" is too high.
"Nominal value current" x transmission
factor current generates a secondary cur-
rent measured variable which exceeds its
value range.
Select the permissible value in A so that
the secondary measuring current of 6 A is
not exceeded. The transmission factor
current is calculated from "Current trans-
former primary current [A]" / "Current
transformer secondary current [A]"
DF 80 E1 56 "Nominal value voltage [V]" is too high.
"Nominal value voltage" x transmission
factor voltage generates a secondary volt-
age measured variable which exceeds its
value range.
Select the permissible value in V so that
the secondary measuring voltage of 300
V is not exceeded. The transmission
factor voltage is calculated from "Voltage
transformer primary voltage [V]" / "Volt-
age transformer secondary voltage [V]"