User data variants
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
206 Manual, 07/2018, A5E42674880-AA
Total power L1L2L3 (ID 254 or FE
H
)
Table D- 2 Total power L1L2L3
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
254 (FE
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L1
UINT
1 mA
0 … 65535
66007
4 ... 5
Current L2
UINT
1 mA
0 … 65535
66008
6 ... 7
Current L3
UINT
1 mA
0 … 65535
66009
8 ... 9
Total active power L1L2L3
INT
1 W
-27648 … 27648
66034
10 ... 11
Total reactive power Qtot L1L2L3
INT
1 var
-27648 … 27648
66038
12 ... 13
Total apparent power L1L2L3
INT
1 VA
-27648 … 27648
66036
14 ... 17 Total active energy L1L2L3 DINT 1 Wh -2147483647...
+2147483647
225
18 ... 21 Total reactive energy L1L2L3 DINT 1 varh -2147483647...
+2147483647
226
22
Reserved
BYTE
-
0
-
23
Total power factor L1L2L3
USINT
0.01
0 … 100
66037
24
Scaling current L1
USINT
-
0 ... 255
-
25
Scaling current L2
USINT
-
0 ... 255
-
26
Scaling current L3
USINT
-
0 ... 255
-
27
Scaling total active power L1L2L3
USINT
-
0 ... 255
-
28
Scaling total reactive power L1L2L3
USINT
-
0 ... 255
-
29
Scaling total apparent power L1L2L3
USINT
-
0 ... 255
-
30
Scaling total active energy L1L2L3
USINT
-
0 ... 255
-
31
Scaling total reactive energy L1L2L3
USINT
-
0 ... 255
-